CET Electric Technology Inc.

PMC-S963-C low-cost digital power/energy meter

PMC-S963-C low-cost digital power/energy meter

Phase:Three-Phase

Installation:35mm DIN Rail

Communication:RS-485,LoRa, Lorawan

Rated Current:5A/1A

Frequency:45Hz-65Hz

Inputs and Outputs:Optional 4xDI, 2xDO, 4xRTD, 1xIr, 2xSS Pulse Output

Output Voltage:20-277V L-N/35-480V L-L

Accuracy Class:IEC 62053-22: 2020 Class 0.5S

Dimensions(mm):72(W)x95(H)x70(D)

 

 

 

 

  • Product Details
  • Parameter
  • Device View and Dimensions

   LFP battery, fire resistant, non-toxic, and redundant system level protection

   12cm ultra-thin body, providing flexible placement options

√  Easily increase capacity using modular batteries and enclosures 

  Self-developed BMS with excellent battery capacity balancing ability

Accuracy

Parameters Accuracy Resolution
Voltage

±0.2%

0.001V
Current

±0.2%

0.001A

I4 (measurement)

±0.2%

0.001A

Ir (measurement)

±0.5%

0.001A

P, Q, S

±0.5%

0.001kX

kWh, kVAh

5A/1A Option

IEC 62053-22 Class 0.5S

ANSI C12.20 Class 0.2

0.1kXh

SCCT Option

IEC 62053-21 Class 1

kvarh

5A/1A Option

IEC 62053-24 Class 0.5S

IEC 62053-23 Class 2

0.01kvarh

SCCT Option

IEC 62053-24 Class 1

IEC 62053-23 Class 2

PF

±0.5%

0.001

Frequency

±0.02Hz

0.01Hz

THD

IEC 61000-4-7 Class B

0.001%

K-Factor

IEC 61000-4-7 Class B

0.001

Phase Angle

±1°

0.1°

 

Technical Specifications

 

Voltage Inputs (V1, V2, V3, VN)

Standard Un

400ULN/690ULL

Range

10V to 1.2Un

Overload

1.2xUn continuous, 2xUn for 1s

Burden

<0.02VA per phase

Measurement Category

CAT III up to 600ULL

Frequency

45-65Hz 

 

Current Inputs (I11, I12, I21, I22, I31, I32)

Standard In

Standard 5A, Optional 1A

SCCT Options

100A/200A/400A/800A/1600A to 40mA Output

Range

0.1% to 200% In

Starting Current

0.1% In

Overload

2xIn continuous, 20xIn for 1s

Measurement Category

CAT III up to 600ULL

Burden

<0.15VA per phase @ 5A

 

Power Supply (L+, N-)

Standard

95-250VAC/DC, ±10%, 47-440Hz

Optional

20-60VDC

Burden

<3W

Overvoltage Category

CAT III up to 300ULN

 

Digital Inputs (DI1, DI2, DI3, DI4, DIC)

Type

Dry contact, 24VDC internally wetted

Sampling

1000Hz

Hysteresis

1ms minimum

 

Digital Outputs (DO11, DO12, DO21, DO22)

Type

Form A Mechanical Relay

Loading

5A @ 250VAC or 30VDC

 

Optional SS Pulse Outputs (E1+, E1-, E2+, E2-)

Type

Form A Solid State Relay

Isolation

Optical

Maximum Load Voltage

50VDC

Maximum Forward Current

50mA

 

 