- Product Details
- Parameter
Technical Specifications
Voltage (Un) |
220-240VLN |
|
Overrange (% Un) |
110%-120% |
|
Range (V) |
168 to 264VAC |
|
Burden |
<10VA/phase |
|
Frequency |
45-65Hz |
|
Direct Input |
Current (Ib/Imax) |
20A/100A |
Range |
0.4% Ib to Imax |
|
Starting Current (Ist) |
0.4% Ib (0.08A) |
|
Minimum Current (Imin) |
5% Ib (1A) |
|
Burden |
<4VA/phase |
|
Power Supply |
Self-powered 168 to 264VAC |
|
Maximum Wire Size |
35mm2 (3AWG) |
|
Maximum Torque |
2.5 N.m |
|
CT Input |
Current (In/Imax) |
5A/6A |
Range |
(0.1%-120%) In |
|
Starting Current (Ist) |
0.1% In |
|
Burden |
<0.5VA/phase |
SS Pulse Output
Pulse Constant |
1/10/100/500*/1000 /3200/5000* imp/kWh (imp/kvarh) |
|
Isolation |
Optical |
|
Max. Load Voltage |
80V |
|
Max. Forward Current |
50mA |
|
Pulse Width |
60-150ms (PMC-340-A) 30-150ms (PMC-340-B) |
Communications
RS-485 |
Modbus RTU |
|
Baud Rate |
1200/2400/4800/ 9600/19200 bps |
|
Maximum Wire Size |
1.5mm2 (16AWG) |
|
Maximum Torque |
0.45 N.m |
Accuracy
Parameters | Accuracy | Resolution | |
Voltage (U) |
±0.5% |
0.01V |
|
Current (I) |
±0.5% |
0.001A |
|
kW, kVA |
±1.0% |
0.01kX |
|
kvar |
±1.0% |
0.01kvar |
|
kvarh |
IEC62053-23: 2020 Class 2 |
0.01kvarh |
|
kWh kVAh |
IEC62053-21: 2020 Class 0.5 for 100A Direct Input |
0.1kXh (PMC-340-A) 0.01kXh (PMC-340-B) |
|
IEC62053-22: 2020 Class 0.5S for 5A CT Input |
|||
PF |
±1.0% |
0.001 |
|
Frequency |
±0.02Hz |
0.001Hz |
|
Harmonics |
IEC61000-4-7 Class II |
0.1% |