CET Electric Technology Inc.

PMC-53A-E Ethernet Multifunction Meter

PMC-53A-E Ethernet Multifunction Meter

Phase:Three-Phase

Installation:DIN 96 (92 x 92 mm Cutout)

Communication:1 x Ethernet, 1 x RS-485

Rated Current:5A (Optional 1A)

Frequency:45 Hz-65 Hz

Inputs and Outputs:4 x DI, 2 x DO, 1 x I4, 1 x Ir and 1 x AI

Input Voltage:400 ULN/ 690 ULL

Accuracy Class: IEC 62053-22 Class 0.5 S

Dimensions(mm):96(W) x 96(H) x 88(D)

  • Product Details
  • Parameter

Product Overview

PMC-53A-E Ethernet Multifunction Meter is CET’s latest offer for the digital power/energy metering market. Housed in a standard DIN form factor measuring 96x96x88mm, it is perfectly suited for industrial, commercial and utility applications requiring direct Ethernet connectivity.

The PMC-53A-E features quality construction, multifunction measurements and a large, backlit, Dot-Matrix LCD that is easy to navigate and user friendly. Compliance with the IEC 62053-22 Class 0.5S and ANSI C12.20 Class 0.2 Standards, it is a cost-effective replacement for analog instrumentation and is capable of displaying 4 measurements at once. It also optionally provides an I4 input for Neutral Current Measurement, one 0/4-20mA Analog Input for measuring external transducer signal as well as an Ir Input for Residual Current Measurement. With a standard 100BaseT Ethernet Port and an RS-485 port supporting multiple protocols, the PMC-53A-E can be easily integrated into Energy Management Systems as well as Building and Utility Automation Systems.

Dimension

Dimensional drawing
install

Application

Send us a message

Sincerely looking forward to working with you!

Accuracy

Parameters Accuracy Resolution
Voltage

±0.2%

0.001V
Current

±0.2%

0.001A

I4 (measurement)

±0.2%

0.001A

Ir (measurement)

±0.5%

0.001A

P, Q, S

±0.5%

0.001kX

kWh, kVAh

5A/1A Option

IEC 62053-22 Class 0.5S

ANSI C12.20 Class 0.2

0.1kXh

SCCT Option

IEC 62053-21 Class 1

kvarh

5A/1A Option

IEC 62053-24 Class 0.5S

IEC 62053-23 Class 2

0.01kvarh

SCCT Option

IEC 62053-24 Class 1

IEC 62053-23 Class 2

PF

±0.5%

0.001

Frequency

±0.02Hz

0.01Hz

THD

IEC 61000-4-7 Class II

0.001%

K-Factor

IEC 61000-4-7 Class II

0.001

Phase Angle

±1°

0.1°

Technical Specifications

 

Voltage Inputs (V1, V2, V3, VN)

Standard Un

400ULN/690ULL

Range

10V to 1.2Un

Overload

1.2xUn continuous, 2xUn for 1s

Burden

<0.02VA per phase

Measurement Category

CAT III up to 600ULL

Frequency

45-65Hz

 

Current Inputs (I11, I12, I21, I22, I31, I32)

Standard In

Standard 5A, Optional 1A

SCCT Options

100A/200A/400A/800A/1600A to 40mA Output

Range

0.1% to 200% In

Starting Current

0.1% In

Overload

2xIn continuous, 20xIn for 1s

Measurement Category

CAT III up to 600ULL

Burden

<0.15VA per phase @ 5A

 

Power Supply (L+, N-)

Standard

95-250VAC/DC, ±10%, 47-440Hz

Optional

20-60VDC

Burden

<3W

Overvoltage Category

CAT III up to 300ULN

 

Digital Inputs (DI1, DI2, DI3, DI4, DIC)

Type

Dry contact, 24VDC internally wetted

Sampling

1000Hz

Hysteresis

1ms minimum

 

Digital Outputs (DO11, DO12, DO21, DO22)

Type

Form A Mechanical Relay

Loading

5A @ 250VAC or 30VDC

 

Optional SS Pulse Outputs (E1+, E1-, E2+, E2-)

Type

Form A Solid State Relay

Isolation

Optical

Maximum Load Voltage

50VDC

Maximum Forward Current

50mA

Prev:

Next:

Inquiry

    PersonalBusinessDistributor