- Product Details
- Parameter
Accuracy
Parameters |
Accuracy |
Resolution |
Voltage |
±0.2% |
0.001V |
Current |
±0.2% |
0.001A |
I4 (measurement) |
±0.5% |
0.001A |
P, Q, S |
±0.5% |
0.001kX |
kWh, kVAh |
IEC62053-22 Class 0.5S
ANSI C12.20 Class 0.2
EN50470-1/3: 2006 Class C |
0.1kXh |
kvarh |
IEC62053-24 Class 0.5S
IEC62053-23 Class 2 |
0.1kvarh |
PF |
±0.5% |
0.001 |
Frequency |
±0.02Hz |
0.01Hz |
THD |
IEC61000-4-7 Class B |
0.001% |
K-Factor |
IEC61000-4-7 Class B |
0.001 |
Phase Angle |
±1° |
0.1° |
Technical Specifications
Voltage Inputs (V1, V2, V3, VN)
Standard Un |
400ULN/690ULL |
Range |
10V to 1.2Un |
Overload |
1.2xUn continuous, 2xUn for 1s |
Burden |
<0.02VA per phase |
Measurement Category |
CAT III up to 600ULL |
Frequency |
45-65Hz |
Current Inputs (I11, I12, I21, I22, I31, I32)
Standard In |
5A (Optional 1A) |
Range |
0.1% to 200% In |
Starting Current |
0.1% In |
Overload |
2xIn continuous, 20xIn for 1s |
Measurement Category |
CAT III up to 600ULL |
Burden |
<0.15VA per phase @ 5A |
Power Supply (L+, N-)
Standard |
95-250VAC/DC, ±10%, 47-440Hz |
Optional |
20-60VDC |
Burden |
<2 W |
Overvoltage Category |
CAT III up to 300 ULN |
Digital Inputs (DI1, DI2, DI3, DI4, DIC)
Type |
Dry contact, 24VDC internally wetted |
Sampling |
1000Hz |
Hysteresis |
1ms minimum |
Digital Outputs (DO11, DO12, DO21, DO22)
Type |
Form A Mechanical Relay |
Loading |
5A @ 250VAC or 30VDC |
Load Type |
Resistive |
Pulse Outputs (E1+, E1-, E2+, E2-)
Type |
Form A Solid State Relay |
Isolation |
Optical |
Load Type |
Resistive |
Output |
Optocoupler output as ON-OFF |
Max. Load Voltage |
50VDC |
Max. Forward Current |
50mA |