√ 4MB for Event & Data Recording
√ Optional AS923-1/2/3/4, KR920 or EU868 LoRaWAN Module
√ IEC 62053-21 Class 1 and IEC 62053-23 Class 2
√ Optional Split–Core CT (SCCT)
√ 35 mm DIN mount with Device Dimensions @ 72x95x70 mm
√ 4MB for Event & Data Recording
√ Optional AS923-1/2/3/4, KR920 or EU868 LoRaWAN Module
√ IEC 62053-21 Class 1 and IEC 62053-23 Class 2
√ Optional Split–Core CT (SCCT)
√ 35 mm DIN mount with Device Dimensions @ 72x95x70 mm
Parameters | Accuracy | Resolution | |
Voltage |
±0.2% |
0.001V | |
Current |
±0.2% |
0.001A | |
I4 (measurement) |
±0.2% |
0.001A | |
Ir (measurement) |
±0.5% |
0.001A | |
P, Q, S |
±0.5% |
0.001kX |
|
kWh, kVAh |
5A/1A Option |
IEC 62053-22 Class 0.5S ANSI C12.20 Class 0.2 |
0.1kXh |
SCCT Option |
IEC 62053-21 Class 1 |
||
kvarh |
5A/1A Option |
IEC 62053-24 Class 0.5S IEC 62053-23 Class 2 |
0.01kvarh |
SCCT Option |
IEC 62053-24 Class 1 IEC 62053-23 Class 2 |
||
PF |
±0.5% |
0.001 |
|
Frequency |
±0.02Hz |
0.01Hz |
|
THD |
IEC 61000-4-7 Class B |
0.001% |
|
K-Factor |
IEC 61000-4-7 Class B |
0.001 |
|
Phase Angle |
±1° |
0.1° |
Standard Un |
400ULN/690ULL |
|
Range |
10V to 1.2Un |
|
Overload |
1.2xUn continuous, 2xUn for 1s |
|
Burden |
<0.02VA per phase |
|
Measurement Category |
CAT III up to 600ULL |
|
Frequency |
45-65Hz |
Standard In |
Standard 5A, Optional 1A |
|
SCCT Options |
100A/200A/400A/800A/1600A to 40mA Output |
|
Range |
0.1% to 200% In |
|
Starting Current |
0.1% In |
|
Overload |
2xIn continuous, 20xIn for 1s |
|
Measurement Category |
CAT III up to 600ULL |
|
Burden |
<0.15VA per phase @ 5A |
Standard |
95-250VAC/DC, ±10%, 47-440Hz |
|
Optional |
20-60VDC |
|
Burden |
<3W |
|
Overvoltage Category |
CAT III up to 300ULN |
Type |
Dry contact, 24VDC internally wetted |
|
Sampling |
1000Hz |
|
Hysteresis |
1ms minimum |
Type |
Form A Mechanical Relay |
|
Loading |
5A @ 250VAC or 30VDC |
Type |
Form A Solid State Relay |
|
Isolation |
Optical |
|
Maximum Load Voltage |
50VDC |
|
Maximum Forward Current |
50mA |