Application:HV, MV and LV Applications

Installation:DIN96

Communication:RS-485,Ethernet

Current Input:5A/1A

Power Supply:95-277VAC/VDC ±10%, 47-440 Hz

Frequency:40Hz-72Hz

Input Voltage:400VLN/690VLL +20%

Display:color TFT LCD display

Dimensions(mm):96(W)x 96(H)x 85(D)

  • Product Details
  • Parameter

Technical Specifications

Voltage Inputs (V1, V2, V3, VN, V4, V4N)

Standard (Un) 400 VLN/690 VLL +20%
Range 5 V to 2 Un for 400 VLN nominal
Overload 2 x Un continuous, 4 x Un for 1 s
Burden < 0.5 VA/per phase
PT Ratio Primary 1-1,000,000 V
Secondary 1-1,500 V
V4 Primary 1-1,000,000 V
V4 Secondary 1-1,500 V
Measurement Category CAT III 1000 V
Frequency 40 Hz-60 Hz @ 50 Hz, 48 Hz-72 Hz @ 60 Hz

Current Inputs (·I11, I12, ·I21, I22, ·I31, I32, ·I41, I42)

Standard (In) 5 A (Standard), 1 A (Optional)
Range 1% to 400% In
Starting Current 0.1% In
Overload 4 x In continuous, 10 x In for 1 s
Burden < 0.5 VA/per phase @ 5 A
< 0.1 VA/per phase @ 1 A
CT Ratio Primary 1-30,000 A
Secondary 1-50 A
I4 Primary 1-30,000 A
I4 Secondary 1-50 A
SCCP Options

Split-Core Current Probe

Input @ max. 500mV

SCCPs (50A, 200A, 500A)

Rogowski Coil (5000A max.)

Power Supply (L/+, N/-)

Standard 95-250VAC/VDC ±10%, 47-440 Hz
Optional 20-60VDC
Burden < 14VA/10W @ 250VAC/DC, < 6W @ 24VDC
Overvoltage Category OVC III 300V

Digital Inputs (DIC, DI1, DI2, DI3, DI4, DIC2, DI5, DI6, DI7, DI8)

Standard Dry contact, 24 VDC internally wetted
Sampling 1000 Hz
Hysteresis 1 ms minimum

Digital Outputs (DO11, DO12, DO21, DO22, DO31, DO32, DO41, DO42)

Type Form A Mechanical Relay
Loading 5A @ 250VAC/30VDC

Alarm Output (Alarm)

Loading 5A @ 250VAC or 30VDC

Optional Solid State Pulse Outputs (E1+, E1-, E2+, E2-)

Type Form A Solid State Relay
Isolation Optical
Max. Load Voltage 30VDC
Max. Forward Current 100mA

Optional Analog Inputs (AI1+, AI1-, AI2+, AI2-, SH)

Type 0-20/4-20 mA DC
Overload 24 mA maximum

Optional Temperature Inputs (TC11, TC12, TC21, TC22, SH)

RTD Type 2-Wire PT100 (sensor not included)
Measurement Range -40°C to +200°C