CET Electric Technology Inc.

PMC-352-C Three-Phase LoRa Energy Meter

PMC-352-C Three-Phase LoRa Energy Meter

Phase:Three-Phase

Installation:35mm DIN Rail

Communication:RS-485,LoRa

Current:40mA(SCCT Option),2mA(SCCTA Option)

Frequency:45Hz-65Hz

Inputs and Outputs:3xDI, 4xNTC Inputs

Voltage:277ULN/480ULL

Accuracy Class:IEC62053-21 Class 1

Dimensions(mm):36(W)x90(H)x65(D)

 

 

 

  • Product Details
  • Parameter

Product Overview

The PMC-352-C 3-Phase LoRa DIN Energy Meter is CET’s latest offer for the wireless loT energy monitoring market using the LoRa technology for its wireless communication capability. Designed in a compact DIN form factor measuring 36x65x90mm, it is perfect for energy and condition monitoring applications in space-limited power distribution board.

The PMC-352-C comes standard with 4xNTC Inputs for temperature monitoring and 3xDI for status monitoring. With standard RS-485 and optionally LoRa supporting the Modbus RTU protocol and IEC 62053-21 Class 1 compliance, the PMC-352-C becomes a vital component of an intelligent, distributed and wireless loT based EMS or Condition Monitoring System.

Dimension

Dimensional drawing
Appearance

Application

Send us a message

Sincerely looking forward to working with you!

Accuracy

Parameters Accuracy Resolution
Voltage ±0.5% 0.0001V
Current ±0.5% 0.0001A
kW, kvar, kVA ±1.0% 0.0001kW/kvar/kVA
kWh IEC 62053-21 Class 1 0.01kWh
kvarh IEC 62053-23 Class 2 0.01kvarh
PF ±1.0% 0.0001
Frequency ±0.02Hz 0.0001Hz
THD IEC 61000-4-7 Class B 0.0001%
Temperature ±1℃ 0.001

Technical Specifications

Voltage Inputs (V1, V2, V3, VN)

Voltage (Un) 277ULN/480ULL
Range 40V to 1.2Un

(88V to 550V for Self-Powered option)

Burden <0.02VA/phase
Frequency 45-65Hz

Current Inputs (I11, I12, I21, I22, I31, I32)

SCCT Option SCCTA Option
Current (In) 40mA 2mA
Range 0.15%-100% In 0.1%-120% In
Starting Current 0.15% In 0.2% In
External SCCTs 100A/40mA 5A/2mA
200A/40mA
400A/40mA
800A/40mA
1600A/40mA

Power Supply (L+, N-)

Standard 60-264VAC/DC, ±10%, 47-440Hz
Optional 88V-550VAC, Self-Powered via Uca (U31)
Burden <2W

Digital Inputs (DI1, DI2, DI3, DIC)

Type Dry contact, 12VDC internally wetted
Sampling 1000Hz
Hysteresis 1ms minimum

NTC Temperature Inputs (TC1, TC2, TC3, TC4)

NTC Type 2-Wire Thermistors (sensor not included)
Measurement Range -20°C to +140°C

Communications

RS-485Protocol Protocol Modbus RTU
Baud Rate 1200/2400/4800/9600/

19200/38400 bps

LoRa RF Range 860-935 MHz (Configurable)
ISM Bands EU863-870, RU864-870, IN865-867, US902-

928, AU915-928, AS920-923, AS923-925

RF Output Power 19 dBm (Maximum)
Receiver Sensitivity -137 dBm (Maximum)
Output Watts 0.03 (Typical)
FCC Part 15C Certified by TCB

Environmental Conditions

Operating Temperature -25°C to +70°C
Storage Temperature -40°C to +85°C
Humidity 5% to 95% non-condensing
Atmospheric pressure 70kPa to 106kPa
Pollution Degree 2

Mechanical Characteristics

Unit Dimensions 36(W)x65(D)x90(H)mm
Mounting DIN Rail
IP Rating IP30