CET Electric Technology Inc.

PMC-53A Intelligent Multifunction Meter

PMC-53A Intelligent Multifunction Meter

Phase:Three-Phase

Installation:DIN96 (92x92mm Cutout)

Communication:RS-485

Rated Current:5A/1A

Frequency:45Hz-65Hz

Display:Backlit Dot-Matrix LCD Display

Input Voltage:400ULN/690ULL

Accuracy Class:IEC62053-22 Class 0.5S

Dimensions(mm):96(W)x96(H)x88(D)

  • Product Details
  • Parameter

Product Overview

PMC-53A Intelligent Multifunction Meter is CET’s latest offer for the low-cost digital power/energy metering market. Housed in a standard DIN form factor measuring 96x96x88mm, it is perfectly suited for industrial, commercial and utility applications.

The PMC-53A features quality construction, multifunction measurements and a large, backlit, Dot-Matrix LCD that is easy to navigate and user friendly. Compliance with the IEC62053-22 Class 0.5S, ANSI C12.20 Class 0.2 and EN50470-1/3 Class C Standards, it is a cost-effective replacement for analog instrumentation and is capable of displaying 4 measurements at once. It optionally provides I4 input for Neutral Current measurement, a second RS-485 port, up to six Digital Inputs for status monitoring, four Relay Outputs for control and alarm applications as well as other I/O options for different applications.

Dimension

Dimensional drawing
install

Application

Send us a message

Sincerely looking forward to working with you!

Accuracy

Parameters Accuracy Resolution
Voltage ±0.2% 0.001V
Current ±0.2% 0.001A
I4 (measurement) ±0.5% 0.001A
P, Q, S ±0.5% 0.001kX
kWh, kVAh IEC62053-22 Class 0.5S

ANSI C12.20 Class 0.2

EN50470-1/3: 2006 Class C

0.1kXh
kvarh IEC62053-24 Class 0.5S

IEC62053-23 Class 2

0.1kvarh
PF ±0.5% 0.001
Frequency ±0.02Hz 0.01Hz
THD IEC61000-4-7 Class B 0.001%
K-Factor IEC61000-4-7 Class B 0.001
Phase Angle ±1° 0.1°

Technical Specifications

Voltage Inputs (V1, V2, V3, VN)

Standard Un 400ULN/690ULL
Range 10V to 1.2Un
Overload 1.2xUn continuous, 2xUn for 1s
Burden <0.02VA per phase
Measurement Category CAT III up to 600ULL
Frequency 45-65Hz

Current Inputs (I11, I12, I21, I22, I31, I32)

Standard In 5A (Optional 1A)
Range 0.1% to 200% In
Starting Current 0.1% In
Overload 2xIn continuous, 20xIn for 1s
Measurement Category CAT III up to 600ULL
Burden <0.15VA per phase @ 5A

Power Supply (L+, N-)

Standard 95-250VAC/DC, ±10%, 47-440Hz
Optional 20-60VDC
Burden <2 W
Overvoltage Category CAT III up to 300 ULN

Digital Inputs (DI1, DI2, DI3, DI4, DIC)

Type Dry contact, 24VDC internally wetted
Sampling 1000Hz
Hysteresis 1ms minimum

Digital Outputs (DO11, DO12, DO21, DO22)

Type Form A Mechanical Relay
Loading 5A @ 250VAC or 30VDC
Load Type Resistive

Pulse Outputs (E1+, E1-, E2+, E2-)

Type Form A Solid State Relay
Isolation Optical
Load Type Resistive
Output Optocoupler output as ON-OFF
Max. Load Voltage 50VDC
Max. Forward Current 50mA

Prev:

Next:

Inquiry